Linea 14: Linea 14:
   * Perform a Battery Constants check.   * Perform a Battery Constants check.
   * Start a Hyperterminal session with the UPS.  Note: Ensure that there are no accessories plugged into the UPS. (Web Management cards, IO Relay cards etc)   * Start a Hyperterminal session with the UPS.  Note: Ensure that there are no accessories plugged into the UPS. (Web Management cards, IO Relay cards etc)
-  * Start Hyperterminal by going to Start, Programs, Accessories, Communications, Hyperterminal. +  * Start Hyperterminal by going to Start, Programs, Accessories, Communications, Hyperterminal. You will be requested to enter a name and a symbol. Enter a favourite name and click on OK. When a message that a modem must be installed appears, you can ignore this message. Select the serial port to which black serial cable is connected to.  The correct settings for the COM-connection are 2400 Baud, 8 data bits, 1 Stop bit, no parity, protocol Xon/Xoff. In this window, click on Advanced and make sure that the option FIFO activated is unchecked. Click twice on OK. 
-    You will be requested to enter a name and a symbol. Enter a favourite name and click on OK. When a message that a modem must be installed appears, you can ignore this message. +  Check if there is a connection (Type Shift + Y, should return **SM** ). Do not enter any other characters via Hyperterminal other than that described in these instructions because this can cause irreparable damage to the UPS 
-    Select the serial port to which black serial cable is connected to.  The correct settings for the COM-connection are 2400 Baud, 8 data bits, 1 Stop bit, no parity, protocol Xon/Xoff. In this window, click on Advanced and make sure that the option FIFO activated is unchecked. Click twice on OK. +  * Type **1**, wait 2-3 secs and type **1** again (Should return **Prog**) 
-    Check if there is a connection (Type Shift + Y, should return **SM** ). Do not enter any other characters via Hyperterminal other than that described in these instructions because this can cause irreparable damage to the UPS +  Enter a **0** and the UPS reports the present value of the battery constant.  If this value does not correspond to the default value that was given to you by RM Support or APC , it must be changed. 
-   * Type **1**, wait 2-3 secs and type **1** again (Should return **Prog**) +  If this value is not correct, press **+** or **-** until the correct value is returned. 
-    Enter a **0** and the UPS reports the present value of the battery constant.  If this value does not correspond to the default value that was given to you by RM Support or APC , it must be changed. +  Press **R** to close the session. (Should return **Bye**) 
-    If this value is not correct, press **+** or **-** until the correct value is returned. +  Enter **<Shift> Y**, the UPS reports again with **SM**. 
-    Press **R** to close the session. (Should return **Bye**) +  Enter **0** once again and check if the UPS reports back the standard setting that has been set. 
-    Enter **<Shift> Y**, the UPS reports again with **SM**. +  Close Hyperterminal, start the UPS again and check the UPS runtime in the management software.
-    Enter **0** once again and check if the UPS reports back the standard setting that has been set. +
-    Close Hyperterminal, start the UPS again and check the UPS runtime in the management software. +