apc:resetbattery
Differenze
Queste sono le differenze tra la revisione selezionata e la versione attuale della pagina.
Prossima revisione | Revisione precedente | ||
apc:resetbattery [04/12/2018 12:02] – creata djbx83 | apc:resetbattery [28/03/2024 22:24] (versione attuale) – modifica esterna 127.0.0.1 | ||
---|---|---|---|
Linea 1: | Linea 1: | ||
- | Please shut off all connected load, switch off the UPS, pull the power plug of the UPS. | + | [[:start|Torna all' |
- | Switch off the UPS once again till you hear a click. | + | |
- | Remove all accompanying devices. | + | |
- | Turn on the UPS again and connect a computer with Windows 95/98/ME, Windows NT 4.0 or Win 2000, which runs on Hyperterminal using one of the cables mentioned under the requirements. | + | |
- | Close Powerchute plus-Server. With Windows NT/2000, the UPS service must be stopped. If you are using PowerChute Business Edition, stop the Agent *V service. | + | |
- | Perform a Battery Constants check. | + | |
- | Start a Hyperterminal session with the UPS. Note: Ensure that there are no accessories plugged into the UPS. (Web Management cards, IO Relay cards etc) | + | |
- | Start Hyperterminal by going to Start, Programs, Accessories, | + | |
- | You will be requested to enter a name and a symbol. Enter a favourite name and click on OK. When a message that a modem must be installed appears, you can ignore this message. | + | |
- | Select the serial port to which black serial cable is connected to. The correct settings for the COM-connection are 2400 Baud, 8 data bits, 1 Stop bit, no parity, protocol Xon/Xoff. In this window, click on Advanced and make sure that the option FIFO activated is unchecked. Click twice on OK. | + | |
- | Check if there is a connection (Type Shift + Y, should return **SM** ). Do not enter any other characters via Hyperterminal other than that described in these instructions because this can cause irreparable damage to the UPS | + | |
- | Type **1**, wait 2-3 secs and type **1** again (Should return **Prog**) | + | |
- | Enter a **0** and the UPS reports the present value of the battery constant. | + | |
- | If this value is not correct, press **+** or **-** until the correct value is returned. | + | |
- | Press **R** to close the session. (Should return **Bye**) | + | |
- | Enter **< | + | |
- | Enter **0** once again and check if the UPS reports back the standard setting that has been set. | + | |
- | Close Hyperterminal, | + | |
+ | ***** Reset manuale contatore batteria ***** | ||
+ | |||
+ | A volte, a seguito di operazioni di calibrazione errate, può capitare che il contatore interno dell' | ||
+ | |||
+ | Munirsi di cavo Seriale APC e seguire le seguenti istruzioni: | ||
+ | |||
+ | * Please shut off all connected load, switch off the UPS, pull the power plug of the UPS. | ||
+ | * Switch off the UPS once again till you hear a click. | ||
+ | * Remove all accompanying devices. | ||
+ | * Turn on the UPS again and connect a computer with Windows 95/98/ME, Windows NT 4.0 or Win 2000, which runs on Hyperterminal using one of the cables mentioned under the requirements. | ||
+ | * Close Powerchute plus-Server. With Windows NT/2000, the UPS service must be stopped. If you are using PowerChute Business Edition, stop the Agent *V service. | ||
+ | * Perform a Battery Constants check. | ||
+ | * Start a Hyperterminal session with the UPS. Note: Ensure that there are no accessories plugged into the UPS. (Web Management cards, IO Relay cards etc) | ||
+ | * Start Hyperterminal by going to Start, Programs, Accessories, | ||
+ | * Check if there is a connection (Type Shift + Y, should return **SM** ). Do not enter any other characters via Hyperterminal other than that described in these instructions because this can cause irreparable damage to the UPS | ||
+ | * Type **1**, wait 2-3 secs and type **1** again (Should return **Prog**) | ||
+ | * Enter a **0** and the UPS reports the present value of the battery constant. | ||
+ | * If this value is not correct, press **+** or **-** until the correct value is returned. | ||
+ | * Press **R** to close the session. (Should return **Bye**) | ||
+ | * Enter **< | ||
+ | * Enter **0** once again and check if the UPS reports back the standard setting that has been set. | ||
+ | * Close Hyperterminal, |